One of the major benefits of having a geothermal borefield is that you can rely on free and passive geothermal cooling, where the cold in the ground is used directly without the need for a heat pump. The downside of passive cooling is that it puts quite a strict limit on the maximum allowed fluid temperature in order to ensure enough cooling capacity. With the increasing cooling demand due to climate change, this leads to significantly larger borefields. In this chapter, we’ll discuss a different way of approaching geothermal cooling with borefields.
The design challenge
Shallow geothermal systems have gained significant interest in the energy transition due to their ability to provide users with passive cooling. Here, ‘passive’ means that no heat pump is required to cool the building, as we directly utilise the cold stored in the ground (hence the alternative term: ‘free cooling’).
To use this cold directly, we must ensure that our average fluid temperature does not exceed a certain limit, typically set between 16 and 18 °C, because otherwise the fluid in our building’s emission system will not be able to provide the required cooling. Sizing borefields for passive cooling, especially when there are large cooling peaks, requires adhering to very strict temperature limits, increasing the required borefield size for buildings with a high cooling demand.
A potential solution that is often applied in warmer countries is to forgo passive cooling and size the borefield to operate with active cooling instead, using a heat pump to cool the building. This consumes more electricity but removes the restriction of staying below the 16–18 °C limit for passive cooling. Hence, active cooling results in a smaller borefield but with a higher operational cost.
Active cooling just means that the cold is created in an active way, implying a compressor is working somewhere to create the cooling. One can therefore distinguish different active cooling systems. Some options are listed below:
- Reversible heat pumps can change their refrigeration cycle so that the evaporator becomes the condensor and vise versa, providing active cooling to the building and dumping the heat into the ground.
- Hydraulically reversed heat pump Not all heat pumps can change the flow direction of their refrigirant, but it is always possible to hydraulically change the evaporator and condensor of the heat pump. This has in the end the same effect, but more valves and junctions are required to hydraulically change both sides of the machine.
- Heat dump via extra heat exchanger When the ground-source heat pump and the passive heat exchanger stay in series, where the heat exchanger comes hydraulically after the heat pump, everything is already in place to provide active cooling. In fact, when the heat pump turns on, the passive heat exchanger will receive colder fluid temperatures, and therefore enter an ‘active’ mode. When however the building has no heat demand, the heat produced by the heat pump should be dumped back into the ground which can be done by installing another heat exchanger after the passive heat exchanger to dump the heat back into the ground.
Depending on your particular project and hydraulic scheme, there are many different options to create active cooling conceptually.
Two example buildings
To illustrate the difference in both the required borefield size and the electricity usage, let us examine two typical cases where the combination of active and passive cooling is relevant: a heating-dominated auditorium building with some significant cooling peaks, and an office building which generally has a very pronounced cooling demand.
In all the cases below, 25 v/v% MPG is used, with a variable flow rate based on a constant temperature difference of 3 K, and a double-U DN32 PN16 heat exchanger probe.
Auditorium building
An auditorium in a Central European climate typically has a higher annual heating demand than cooling demand, but often experiences a higher cooling peak than heating peak. This is because heating is often delivered via a slow emission system like underfloor heating, whereas cooling is provided via an all-air system. The hourly load profile is given below.
As can be seen, the cooling peak of 90 kW is significantly higher than the heating peak of around 30 kW, but from an energy perspective, this auditorium has much more heating demand than cooling demand.
To meet the cooling demand passively, the average fluid temperature should stay below 17 °C. This requires a borefield of 24 boreholes of 100 m, resulting in the temperature profile below.
In the case of active cooling (with an assumed SEER of 5), the maximum average fluid temperature can be 25 °C. This results in a significantly smaller borefield of 9 boreholes of 120 m, with the temperature profile shown below.
When comparing the two designs, two aspects are important: the required borefield size (which is linked to the investment cost) and the yearly electricity consumption. The total required borehole length is 2376 m in the passive case and 1071 m in the active case, which is a reduction of 55% in borefield size. In contrast, the yearly electricity usage is 193 kWh/year for the passive design and 772 kWh/year for the active one, an increase of 300%.
Office building
Due to the high internal loads from laptops, computers, people, etc., office buildings tend to have a rather high cooling demand, both in terms of peak power and on a yearly basis. The hourly load profile of an example office building is given below.
As with the auditorium building, the cooling peaks are higher than the heating ones, but the yearly cooling load is very similar to the yearly heating demand (both rounded to 118 MWh/year), leading to an injection-dominated borefield when the efficiency of the ground-source heat pump is taken into account.
When a geothermal design is made for the building above considering only passive cooling, the required borefield size is 126 boreholes of 150 m and the resulting temperature profile is given below.
Once again, designing the field for passive cooling leaves us with an enormously oversized borefield with respect to the heating load, with the average fluid temperature almost always staying above 10 °C. When the same design is now made for active cooling, a required borefield of 70 boreholes of 100 m is found, with the following temperature profile.
In the active case above, the injection-dominated character of the borefield is even more visible, with the maximum fluid temperature clearly limiting the design in the last year of the simulation.
When the two designs are compared, the required total borehole length was 18744 m for the passive case and 6930 m for the active case, a reduction of 63%. On the other hand, the yearly electricity usage for cooling went from 5914 kWh/year for the passive case to 23660 kWh/year for the active case, a fourfold increase.
In both cases, the advantages and disadvantages of the active and passive designs are clearly visible. Therefore, the remaining question is: can we combine them? Can we use the cheaper, active design while still benefiting from the lower electricity consumption of the passive one? Can we combine active and passive cooling?
Design methodology
There are two ways to approach the design challenge at hand. The first option is to work with a central change-over that defaults to active cooling during the summer months. The second, more dynamic approach is to work with passive cooling as long as the average fluid temperature is below a certain threshold, and to switch to active cooling when a specific temperature threshold is exceeded. Both methods have different implications for the resulting cooling efficiency and will be discussed below, together with the numerical results for the auditorium and office buildings.
Strictly speaking, it is possible for active and passive cooling to occur simultaneously. Imagine the case where the passive heat exchanger is placed after a heat pump operating in cooling mode. This implies that the fluid leaving the heat pump and entering the heat exchanger is warmer than the fluid that originally entered the heat pump. Now, if the fluid entering the heat pump is cold enough, the fluid entering the heat exchanger may still be cold enough to provide passive cooling to the building.
Typically, when the geothermal fluid is that cold, active cooling is not required, but in some industrial processes, where temperatures of 0–5 °C are required, this situation can occur.
In that case, you can replace the hourly heating load with the extraction load and directly account for the active cooling there. Afterwards, set the heating efficiency extremely high, indicating that it is a ground load that is being simulated. Whatever remains as cooling demand is the regular cooling, which, depending on the fluid temperature, can be active or passive.
Active cooling in fixed months
One very straightforward way to combine active and passive cooling is to use active cooling exclusively during specific months. This approach is similar to a central change-over system where, depending on the cooling demand, a central control decision is taken to switch to active cooling.
This method involves setting the efficiency for both active and passive cooling and determining the months in which active cooling will be used. Based on this information, the algorithm sets the correct efficiency at each moment and generates the corresponding temperature profile as well as the average SEER for the entire simulation period.
In the following two subsections, the results for the auditorium and office building are given when active cooling is used by default in June, July and August.
Auditorium
For the auditorium, the resulting cooling profile is given below.
As can be seen, most of the cooling is active, with a high passive cooling spike right before summer. The resulting yearly average SEER is therefore 5.24, with active cooling accounting for 94% of the cooling demand. This results in a yearly electricity usage for cooling of around 736 kWh/year, which is only slightly lower than the 772 kWh/year of the purely active case.
Office
Below, the same profile is shown for the office building.
In the office building, the cooling season is longer, resulting in a higher SEER of 6.21, with a passive cooling share of 26% (significantly higher than in the auditorium case). This means that the cooling demand requires 19 MWh/year of electricity instead of 23.7 MWh/year in the purely active case, whilst still keeping the same active design.
Although the two results above already show some potential in combining active and passive cooling, there is more to be gained, since, even in the active cooling months, there are periods with lower cooling powers that could be delivered passively, further increasing the overall cooling efficiency. This can be done using the methodology below.
Active cooling above a threshold
Another approach to combining active and passive cooling is based on the principle ‘passive when possible, active when necessary’, aiming to maximise passive cooling. This method involves setting a threshold on the average fluid temperature. If, at a certain hour, there is a cooling demand and the fluid temperature remains below this threshold, passive cooling is used. If it exceeds the threshold, the heat pump is turned on to provide the cooling actively.
This method works as follows:
- Set the efficiency for active and passive cooling.
- Set the temperature threshold above which active cooling is used.
- Calculate the resulting ground load, assuming only passive cooling.
- Calculate the temperature profile.
- Check whether the maximum average fluid temperature is above the passive threshold.
- If yes, recalculate the resulting ground load, treating every hour in which the temperature is above the threshold as active cooling.
- If no, go to step 7.
- Recalculate the temperature profile/size the borefield.
- Return the average SEER.
In the following two subsections, the results for the auditorium and office building are shown.
Auditorium building
In the graph below, the active and passive cooling loads are shown when a temperature threshold of 17 °C is used.
As can be seen, a lot of passive cooling is still possible in the warm summer months, although the highest cooling peaks remain active. The average SEER is 14.49, with a passive cooling share of 87%. This is significantly higher than the 6% obtained when a fixed active cooling period was set. The yearly average electricity usage for cooling is now 267 kWh/year, which is much closer to that of the purely passive case (193 kWh/year), while requiring only 1071 m of borehole length instead of 2376 m.
Due to the yearly imbalance towards extraction, the ground cools down year after year, meaning that the share of active cooling also decreases over time. This is shown in the graph below, where it is clear that the share of active cooling levels out at 10% in the later years.
Office building
For the office building, the same cooling power graph is shown below.
As with the auditorium building, a large share of the summer cooling can be provided passively, resulting in an average SEER of 8.34, corresponding to a passive share of 53%. This means that the electricity consumption for cooling is now around 14 MWh/year instead of 19 MWh/year when a fixed period was used. This is, of course, still significantly more than the 5.9 MWh/year for the purely passive case, but it is important to recall that this design requires only 6930 m of borehole length instead of 18744 m.
The reason why this SEER is lower than in the auditorium example has to do with the injection-dominated imbalance. Year after year, the borefield heats up, reducing both the share of passive cooling and the yearly average SEER. This is shown in the graph below.
In the graph above, the active cooling share starts at 37% in the first year but rises to more than 50% by the 25th year. So, whereas the auditorium building has a decreasing share of active cooling over the years, here it is the other way around.
A note on sustainability
We started off this chapter by stating that the main advantage of geothermal borefields is the ability to provide passive cooling, and we moved towards a discussion of the ideal share of active cooling. Did we lose sustainable cooling somewhere along the way?
It is true that in some regions active cooling is seen as a ‘bad’ or ‘unsustainable’ thing, with regulations sometimes even requiring that a ground-source heat pump cannot deliver active cooling before a subsidy is granted. In the following paragraphs, we want to add some nuance to this claim by giving a few arguments as to why, in our opinion, active cooling is far from unsustainable, although passive cooling is of course preferable.
- Less disruption of the ground
When using passive cooling only, we can save on electricity, but this comes at the cost of a larger geothermal borefield. And although borefields are considered a sustainable technology, they are still permanent constructions in the ground that require materials and fuel for the drilling rigs. A larger borefield therefore also implies a larger environmental impact. By allowing active cooling, borefields can be made smaller and the disruption of the subsurface can be minimised. - Sustainable electricity in summer
Although active cooling requires more electricity than passive cooling, it is important to note that this demand coincides with the highest production of sustainable electricity from, for example, solar PV panels. This implies that, although the electricity usage is higher, the electricity is CO2-neutral, which makes the whole ‘sustainability’ issue questionable, since using something that is not harmful to the environment cannot simply be called ‘a bad thing’. - Best alternative for high cooling loads
In some regions, where it is really warm, there is simply no way around active cooling if we want to provide our buildings with the required summer comfort. For these projects, the question is not whether to opt for active cooling, but whether that active cooling uses the ground or the air. When the comparison is made like that, cooling with a ground-source heat pump is highly preferable: the efficiency is higher (the ground is typically colder than the air), the heat is not lost but stored for high-efficiency heating in winter, and we do not contribute to the urban heat island effect. (More on this in Part 1.1.) - Emission trading system
A final point applies especially to Europe. In Europe, the total yearly amount of CO2 emitted by industry, electricity producers and even intra-European flights is capped, meaning that it is known a priori how much CO2 will be emitted each year. Companies can therefore either lower their emissions or buy the right to emit CO2 on the market. The highest price ever paid to date for 1 tonne of CO2 emissions was €104.
If you have the budget to opt for 100% passive geothermal cooling and an oversized borefield, it could be worth checking how much money you would save with an active–passive combination, and using the remaining budget to buy CO2 certificates. The positive impact on global emissions would be 100 times greater than if you invested in purely passive cooling.
Conclusion
In this chapter, the focus was on active and passive cooling, each with its own advantages and disadvantages. A system with active cooling can have a substantially lower investment cost but comes with a higher electricity consumption. For the passive case, the situation is reversed, with a higher investment cost for the borefield and a lower running cost.
Two different algorithms were introduced to combine the positive aspects of both methods: the cheaper borefield of active cooling with the higher efficiency of passive cooling. It was shown that, when both are combined using a temperature threshold, more than 50% of the entire cooling load can still be provided passively, making this combination extremely powerful for achieving economically feasible designs when there is a high cooling demand.
Lastly, on a more general note, some arguments were given as to why active cooling is not as unsustainable as is sometimes claimed.
Questions
References
- Coninx, M., De Nies, J., Hermans, L., Peere, W., Boydens, W., & Helsen, L. (2024). Cost-efficient cooling of buildings by means of geothermal borefields with active and passive cooling. Applied Energy, 355. https://doi.org/10.1016/j.apenergy.2023.122261
- Peere, W. (2025). Aktiv und passiv: Die perfekte Kombination? Kühlung mit geothermischen Bohrfeldern. Geothermische Energie, 112, 20–21.