Regeneration

Imbalance is one of the most common challenges when it comes to designing geothermal borefields. Although different solutions exist (such as changing your design or opting for a hybrid geothermal system), a common approach is to rely on regeneration to actively counteract the imbalance. In this chapter, we’ll take a deep dive into what regeneration is, which technologies can be used and which algorithms exist, and work through an extensive example in GHEtool Cloud.

What is regeneration?

When designing shallow geothermal borefields, you often have to deal with long-term temperature drift caused by the imbalance of your system. Your borefield will either cool down year after year because the extraction load is higher than the injection load, or vice versa. The temperature profile below shows a borefield with a significant imbalance towards extraction.

Imbalance
Temperature profile of an extraction-dominated borefield.

Such an imbalance is undesirable, since it can lead to a larger required borefield size to ensure that the fluid temperatures stay within the set limits (as discussed in Part 5.4).

Conceptually, there are two different ways to avoid this imbalance: hybridisation and regeneration. The hybridisation option was discussed extensively in the previous part and works by taking part of the building load off the borefield, so that the imbalance is reduced. An example of a Sankey diagram with a hybrid heating technology is shown below.

Sankey diagram of the borefield with a hybrid heating system.
Sankey diagram of the borefield with a hybrid heating system.

The Sankey diagram above clearly shows that the hybrid technology (for example, an air-source heat pump) takes away part of the building’s heating demand, directly reducing the imbalance, since the cooling demand remains identical. This results in the temperature profile below, where the fluid now stays exactly within the predefined limits, but the imbalance is still clearly visible. This also implies that, if the simulation period is extended to, for example, 40 years, the share of the hybrid technology should be increased so that the imbalance is further reduced and the fluid stays within the limits for longer.

Profile after hybrid
Temperature profile for an extraction-dominated borefield with a hybrid system.

Another option is to regenerate the borefield, as shown in the Sankey diagram below. Here, the heating (and DHW) load is still provided entirely by the GSHP, but the imbalance has now completely disappeared. With the help of regeneration, extra heat is injected into the ground, where it is stored in the seasonal thermal energy storage (STES) and later used by the GSHP.

As you may recall from Part 9.1, a hybrid system was defined as a system in which multiple technologies provide the heating and cooling to the building. In the case of regeneration, as can clearly be seen in the Sankey diagram below, 100% of the heating load is still provided by the ground-source heat pump, and the regeneration simply takes the place of the imbalance in the energy flow. For that reason, regeneration is not considered a hybrid technology in GHEtool.
Sankey regeneration
Sankey diagram with regeneration.

The situation above results in the temperature profile below. Here, it is clear that there is no longer any long-term temperature drift, implying that, if the simulation period were extended to 40 years, this would not influence the feasibility of the system.

It is also clear that the profile now looks completely different, since regeneration changes the load profile of the ground by injecting (or extracting) extra heat into (or from) the ground.

Profile after regeneration
Temperature profile after regeneration.

In what follows, the different categories of regeneration technologies will be discussed, after which the details of simulating regeneration (the rules for regeneration, where to place it and which algorithm to pick) will be explained. Finally, with this background knowledge, an in-depth example in GHEtool will be worked through.

Regeneration technologies

Regeneration can be done with almost any technology, as long as it is able to deliver heating, cooling or both. That, in a sense, is the beauty of regeneration. If you have an extraction-dominated borefield, anything that can be used as a heat source is suitable for regeneration and, likewise, any cold source is suitable in the case of an injection-dominated borefield.

In GHEtool Cloud, four categories of regeneration technologies are implemented, into which, with some degree of abstraction, all regeneration technologies can fit. These are discussed below.

Constant power

The first and most straightforward technology category for regeneration is constant power. This implies that we always have a certain amount of power available for either injection or extraction. Think, for example, of an electric heating element that can be turned on at any time to deliver a certain amount of power, or even an air-source heat pump with a certain installed power that it can deliver in heating and/or cooling.

The idea behind a constant power technology is that its power is constant and does not depend on time.

Constant temperature

The counterpart of a regeneration technology with a constant power is one with a constant reference (or regeneration) temperature, with which we can exchange energy via a heat exchanger. Examples include a district heating or cooling network, sewage water or ventilation exhaust air.

All these sources have (to a high degree) a constant, time-independent temperature that can be used for regeneration. For example, the temperature of ventilation exhaust air is typically around 22 °C year-round. When a heat exchanger is installed here and the fluid temperature is colder than this temperature, heat can be extracted from the air and injected into the ground. When the fluid temperature is warmer, heat can be released into the air, cooling down the ground.

The power $\dot{Q}$ in [W] that such a heat exchanger can deliver is proportional to the temperature difference $\Delta T$ between the temperature of the regeneration source and the average fluid temperature in the heat exchanger. When the temperature difference increases, the power the heat exchanger delivers increases as well. In GHEtool, this is assumed to be a linear relationship with a scaling factor $k$ in [W/K]: $$\dot{Q}=k\cdot \Delta T$$

Besides the heat transfer coefficient, $k$, a pinch temperature is also required. This pinch temperature is the temperature loss across the heat exchanger itself and is 0 K for an ideal heat exchanger, meaning that the fluid temperature on one side can exactly match the temperature on the other side. In reality, however, this difference is always greater than 0 K and determines the efficiency of the heat exchanger.

Another way to think about this is that the pinch temperature lowers the reference temperature. For example, if you have a reference temperature of 20 °C and a pinch temperature of 2 K, GHEtool will model the heat exchanger as an ideal one with a reference temperature of 18 °C. You therefore lose two degrees across it.
Be careful when defining this heat transfer coefficient. GHEtool uses the average fluid temperature on the borefield side (the primary fluid temperature), so keep this in mind when defining your heat transfer coefficient. It does not matter which temperature is used for the other side of the heat exchanger (inlet, outlet or average), as long as it matches the constant temperature you provide.

Solar thermal

One very common regeneration technology is solar thermal, such as solar thermal collectors, solar absorbers (also called swimming pool heaters, like the one shown below) or PVT panels. These are all technologies that convert solar radiation into heat and are typically used in situations where the borefield is extraction-dominated.

Example of solar absorbers (unglased collectors). (Source: AQSOL)
Example of solar absorbers (unglased collectors). (Source: AQSOL)

Besides converting (part of) the solar energy into heat, these technologies also exchange energy with the surrounding air. Typically, when solar thermal collectors are used for heat production, this is a heat loss to the environment, but in the case of regeneration, where the fluid temperatures are rather low, it can also be seen as a gain.

The power that solar thermal regeneration technologies can deliver can be written as:

$$\dot{Q}=a_0\cdot \dot{Q}_{sol} \cdot A + a_1\cdot A \cdot \Delta T + a_2\cdot A \cdot (\Delta T)^2$$ where $\dot{Q}_{sol}$ is the solar irradiance in [W/m²], $A$ the surface area in [m²], $\Delta T$ the temperature difference between the surrounding air and the average fluid temperature in the panel, and $a_0$, $a_1$ and $a_2$ the zeroth-, first- and second-order heat loss coefficients.

The formula above also shows that solar thermal panels can be used to extract heat as well, namely when the fluid is warmer than the surrounding air, i.e. when $\Delta T < 0$. This is, however, typically not as efficient as a dry cooler, since even the smallest amount of sunlight heats the fluid back up.

I added two things so the paragraphs use the notation more consistently: $\dot{Q}$ in [W] in the sentence introducing the formula, and “i.e. when $\Delta T < 0$” in the last paragraph. Remove either if you don’t want them.

Dry coolers

Dry coolers (or in fact any sort of heat exchanger with the outside air) are the last category of regeneration technology. Like solar thermal technologies, they depend on the outside environment, but they do not harvest any of the solar irradiance. As with constant temperature regeneration, they act as a heat exchanger with the (now changing) surrounding air, with a regeneration power that is proportional to the temperature difference $\Delta T$ via the heat transfer coefficient $k$. A pinch temperature is also required here, just as for the constant temperature regeneration technology.

The graph below shows a typical performance chart of a dry cooler.

Performance sheet of the AU50 dry cooler of Ecoforest.
Performance sheet of the AU50 dry cooler of Ecoforest.
Depending on the manufacturer of the dry cooler, other definitions might be used for the heat transfer coefficient. In GHEtool, the temperature difference $\Delta T$ is defined as the difference between the air inlet temperature ($T_4$ in the graph below) and the average fluid temperature (the average of $T_1$ and $T_2$).

Dry coolers are very well suited to regenerating both extraction-dominated and injection-dominated borefields.

Known profile

A final option is to work with a known regeneration power profile. For example, when you have a waste heat stream available that can deliver a known power at each hour, or you want to use the known, variable cooling load of a nearby building as a source of regeneration, you can simply upload a CSV file containing the hourly values and whether they are injection or extraction.

Three rules for regeneration

As mentioned, both hybridisation and regeneration solve the same problem of imbalance, but they do so in very different ways. Hybridisation takes part of the load away from the borefield, making the temperature limits less critical. Regeneration does the opposite: it increases the geothermal load so that the imbalance is compensated for, but in doing so, it changes the temperature profile significantly, which can have a considerable impact on future temperatures.

Imagine the case above, with a significant imbalance towards extraction, which we want to compensate for by injecting extra heat into the ground. Ideally, this can be done with some form of solar thermal regeneration in summer (when it is warm and there is quite a lot of sunlight), but this would increase the borehole wall temperature as well as the fluid temperatures, reducing the potential for (passive) cooling.

To overcome this issue, three regeneration rules are applied in the back end.

  1. Do not over-regenerate
    Regeneration is meant to counteract the imbalance, but if you’re not careful, it can create a new imbalance. Imagine the case where regeneration is used to compensate for an extraction-dominated load by injecting extra heat into the ground. If you keep doing that, the borefield will eventually become injection-dominated. Therefore, regeneration should be limited to, at most, the current imbalance.
  2. Do not cross the temperature threshold at the current hour
    Regeneration changes the temperatures at the current hour, and you should ensure that they stay within the set temperature limits. This automatically limits the power you can inject or extract with regeneration.
  3. Do not cross the temperature threshold at a future hour
    Regeneration not only changes the temperature in the hour in which it takes place, but also in the hours that follow. Imagine, for example, that there has been some regeneration by heat injection an hour before a very high cooling load is placed on the borefield. It is possible that, thanks to rule 2, the temperature limit was not crossed during the previous hour, but due to the regeneration, the borefield is slightly warmer when handling the cooling peak, so its limits are crossed.

    To overcome this, every time we regenerate, we would in theory need to check all future hours to make sure that what we do now will not negatively impact the future. However, a simulation horizon equal to the simulation period makes the algorithm unnecessarily slow. In practice, a simulation horizon of at most 4380 hours (i.e. half a year) is typically more than enough, and a shorter horizon often does the trick as well.

By following the three rules set out above, regeneration can take place without the temperature limits being crossed within the simulation horizon.

Even with these rules, some temperature violations can still occur. Imagine, for example, the case where the borefield is extraction-dominated and the cooling peak already causes the fluid temperature to exceed the maximum temperature limit. In that case, regeneration can only make this worse, since the temperature limit was already exceeded before the regeneration started.
Another important aspect that can limit the regeneration power is the flow rate through your regeneration system. In all regeneration technologies where a heat exchanger is used, the temperature of the fluid leaving the heat exchanger can never be higher than that of the fluid on the other side. When the flow rate is low, the temperature difference between the regeneration inlet and outlet will be larger, limiting the power of the regeneration technology. However, when the flow rate is very high, the same regeneration technology (for example, solar thermal) can deliver more power.

Where to place the regeneration

The next important question is: where do I position the regeneration technology? There are two options implemented in GHEtool Cloud: right before the borefield inlet or right after the borefield outlet. Both of these will be discussed briefly below.

Right before the borefield inlet

When the regeneration technology is placed right before the borefield inlet, it receives the coldest fluid during heating and the warmest fluid during cooling, since it is positioned right after the GSHP. This was also discussed in Part 7.1.

This is interesting, for example, for an extraction-dominated borefield that still has some high cooling peaks. In that case, regeneration should happen in winter or in the mid-seasons, to stay as far away as possible from the high cooling peaks. We then want the fluid temperature to be as cold as possible, so that it is easier to inject heat into the ground, which is why we place the regeneration right before the borefield inlet.

Right after the borefield outlet

When the regeneration technology is placed right after the borefield outlet, it receives the warmest temperatures during heating and the coldest ones during cooling.

This could be interesting, for example, when we again have an extraction-dominated borefield, but now there are very few cooling peaks in summer (or they are active, so the maximum fluid temperature does not matter that much). In that case, ideally, the regeneration happens in summer, when the surrounding air is the warmest and the sun shines the brightest. Since in summer, when there is cooling, the outlet position gives the lowest temperatures, this would be the ideal solution.

This shows that, depending on your regeneration technology as well as your building load, the ideal position can be different from case to case, as will be illustrated in the example below.

Regeneration algorithms

The last piece of theoretical background has to do with how the algorithm decides when it could regenerate the borefield. Depending on how you look at this problem, as well as your time horizon of ‘imbalance’, four different algorithms can be defined, each of which corresponds to a control strategy in practice. These will be discussed below.

Yearly

The first, yearly, regeneration algorithm has the purpose of compensating for the imbalance of every year individually. Imagine the case where there is a 20 MWh/year imbalance. In that case, this method will regenerate at most 20 MWh/year (or less, if there is not enough power available to regenerate everything) but not more.

When there is enough regeneration capacity available to compensate for the entire imbalance, this method will yield a temperature profile that is identical every year.

Simulation period

Another way of looking at this problem is by considering the total imbalance over the entire simulation period. Imagine a simulation period of 20 years is considered, with 20 MWh/year of imbalance. This results in 400 MWh that could be regenerated over the entire simulation period. This method will just start regenerating as much as possible as soon as possible until the entire imbalance is compensated for.

This is generally the fastest regeneration method, since it can happen that the borefield is completely balanced before the end of the simulation period. Imagine investing extra in solar thermal panels to compensate for the imbalance. It is possible that these panels inject more heat into the ground than the imbalance in a single year. This implies that, for example, after 15 years the entire imbalance of 20 years has already been compensated for and no regeneration is needed in the last 5 years. This is also shown in the figure below.

Temperature profile with regeneration and the simulation period algorithm.
Temperature profile with regeneration and the simulation period algorithm.

In this method, it can therefore also happen that (in the first years) the imbalance switches from extraction- to injection-dominated in certain years, but since the imbalance is now considered over the entire simulation period, this is still in line with the first regeneration rule above, since at this time scale, there is no over-regeneration.

Proceeding horizon

The two methods above assume some pre-existing knowledge about the imbalance, whereas this is often not known in practice. In the ‘proceeding horizon’ method, the algorithm can only regenerate the imbalance that has already happened; it can therefore only react to it and not anticipate it. This means that, for example, after winter, the sum of all the energy exchange with the ground is typically dominated by extraction, so the algorithm can compensate for that. However, if, somewhere during summer, the imbalance is 0, it will stop regenerating, even if there is more imbalance in the months to come.

In this method, it may be impossible to remove all the imbalance from a certain borefield, since the algorithm cannot anticipate future imbalance like the other two methods can. For example, when part of the extraction imbalance happens in November and December, the algorithm will not have the next summer to compensate for this, leaving behind a small imbalance.

Proceeding horizon +

This last method basically extends the idea behind the previous algorithm, but now regeneration can happen in both directions. Just as before, the imbalance is calculated at every hour based on the sum of all the previous heat injections and extractions. It can happen that, for some profiles, this net resulting imbalance is extraction-dominated before summer and injection-dominated right after summer. In this case, this method will first regenerate with injection and afterwards with extraction, whereas the proceeding horizon method above will only regenerate in the direction of the overall imbalance (either extraction or injection).

Example in GHEtool Cloud

As an example of the advantage of regeneration and the different simulation options, let us consider the residential building from the previous part, which has a significant demand for heating and domestic hot water as well as some high cooling peaks. There is room for a borefield of 40 boreholes. For sustainability reasons, the owner wants to work with pure water instead of antifreeze, which means that the temperature limits are quite strict: the average fluid temperature should stay above 5 °C to avoid local freezing in the heat pump’s evaporator, and below 16 °C to ensure passive or free cooling in summer. A constant flow rate of 8 kg/s is used.

When the borefield is simulated with a simulation period of 40 years, the following temperature profile is obtained.

Hourly temperature profile of the residential building without any regeneration.
Hourly temperature profile of the residential building without any regeneration.

In the temperature profile above, the imbalance is clearly visible. In the first couple of years, both heating and cooling can be provided without any problem, but in the long run the geothermal system will fail due to the low temperature and the use of water as heat transfer fluid. One solution could be to increase the borefield size or to work with antifreeze, but another one is to add a regeneration technology to compensate for the imbalance and make the system work with the existing size. This last option is the one of interest in this chapter.

In the example below, the regeneration will be done using a dry cooler with different sizes to see the influence of the dry cooler sizes on the resulting fluid temperatures.

Although it is possible to run the regeneration algorithms with a simulation period of 40 years, this is not recommended due to the longer computation time. Ideally, you start by comparing different design options with a shorter simulation time (2–5 years) to see their effect and only run for a longer time when you are quite sure about the regeneration technology and size you have selected. That way, you can design regeneration technologies as quickly as possible.

Inlet and outlet

As a first variation, let us consider a dry cooler with a specific heat exchange of 5 kW/K, a 0 °C pinch temperature, a simulation horizon of 4380 hours and the yearly regeneration algorithm. The remaining design choice is whether to place the dry cooler at the borefield inlet or at the outlet.

As mentioned above, depending on your particular project, one or the other can yield more regeneration. In fact, in order to increase the regeneration capacity of any technology that depends on the temperature (i.e. constant temperature, solar thermal and dry cooler regeneration technologies), you want to maximise the temperature difference between the fluid and the air to increase the regenerative power.

When the dry cooler is installed at the inlet of the borefield, the fluid temperatures during extraction (i.e. heating and domestic hot water) will be the coldest, but they’ll be the highest during cooling. Therefore, if you have relatively warm winters and cool summers, this could give you the highest regenerative power.

However, if your winters are cold and summers warm, so that most of the regeneration should happen in summer, it is best to place the dry cooler at the outlet of the borefield, so that the fluid temperatures are the coolest in summer. The final choice is hence strongly dependent on your particular weather profile and building load. In the graph below, the regeneration load is shown for the inlet position.

Regeneration graph for a dry cooler with 5kW/K positioned at the borefield inlet.
Regeneration graph for a dry cooler with 5 kW/K positioned at the borefield inlet.

When the dry cooler is positioned at the borefield inlet, the imbalance drops from 89 MWh/year towards extraction to only 29 MWh/year, due to the 60 MWh/year of regeneration. As can be seen in the graph above, the regeneration takes place throughout the year, and the warmest periods of the year are avoided so that the fluid temperature stays within the limits. The resulting temperature profile is shown below.

Temperature profile for a dry cooler with 5kW/K positioned at the borefield inlet.
Temperature profile for a dry cooler with 5 kW/K positioned at the borefield inlet.

Both in the temperature profile above and in the regeneration graph, it is clear that the dry cooler cannot regenerate much in the first year (there is a big gap in the regeneration power). This is because the ground temperature is still too high in the first year to regenerate a lot, since that would compromise our maximum fluid temperature limit and hence the passive cooling potential in summer.

In the graph below, the regeneration power is shown for a position at the borefield outlet.

Regeneration graph for a dry cooler with 5kW/K positioned at the borefield outlet.
Regeneration graph for a dry cooler with 5 kW/K positioned at the borefield outlet.

Although the effect is subtle, in the case above, the regeneration happens less in the winter and mid-season months and more in the summer and warmer periods. This is precisely due to the colder fluid temperatures in summer and warmer ones in winter. In this particular case, the regeneration for an outlet position is slightly higher, at 63 MWh/year.

In practice, a heat pump – regeneration – borefield configuration is typically more robust and easier to control than when the regeneration is in front of the heat pump. This is because the regeneration power can vary rapidly (especially when using solar thermal technologies), so when the heat pump is placed right after the regeneration, it should be able to cope with potentially high temperature swings. Whenever that is an issue, placing the regeneration at the borefield inlet can be a safer configuration.

Pinch temperature

In the simulation above, the pinch temperature was set to 0 °C, which leads to the theoretical maximum potential. The pinch temperature is defined as the smallest temperature difference between the two sides of a heat exchanger (in the case of a dry cooler, the outside air temperature and the fluid temperature) and is always higher than 0 °C, since there is always some temperature loss across the heat exchanger. Depending on your dry cooler configuration, this pinch temperature will be larger or smaller. With a realistic pinch temperature of 2 °C, the resulting regeneration graph is shown below (again, and from now on, for a position at the borefield inlet).

Regeneration graph for a dry cooler with 5kW/K with a pinch temperature of 2°C.
Regeneration graph for a dry cooler with 5 kW/K with a pinch temperature of 2°C.

As can be seen, there is now less regeneration in total (only 43 MWh/year instead of 60 MWh/year) and almost no regeneration in winter. This is because, conceptually, you need to subtract the pinch temperature from the temperature difference between the air and the fluid, which reduces the regeneration potential.

Different sizes

Without any pinch temperature, the inlet position still left about 29 MWh/year of imbalance, so a logical step, if we want to completely remove the imbalance, is to increase the size of the regeneration technology. When the dry cooler is doubled in size to a 10 kW/K machine, the following regeneration load is obtained (for a 0 °C pinch temperature).

Regeneration graph for a dry cooler with 10 kW/K positioned at the borefield outlet.
Regeneration graph for a dry cooler with 10 kW/K positioned at the borefield outlet.

When the profile above is compared to the 5 kW/K case, it is clear that a 10 kW/K dry cooler gives more regeneration (72 MWh/year instead of 30 MWh/year). However, when the dry cooler size is doubled once again to 20 kW/K, the regeneration load only increases to 77 MWh/year, meaning that for a doubling of the dry cooler size, only a 7% increase in regeneration capacity is obtained. The regeneration graph for the 20 kW/K case is shown below.

Regeneration graph for a dry cooler with 20 kW/K positioned at the borefield outlet.
Regeneration graph for a dry cooler with 20 kW/K positioned at the borefield outlet.

Although the regeneration power is higher in this case (reaching almost 100 kW), the period in summer in which there can be no regeneration due to the maximum temperature threshold becomes longer. This counteracts the positive effect of the higher regeneration power and in the end yields a result that is rather similar to the 10 kW/K case. The temperature profile for the regeneration graph above is shown below.

Temperature profile for a dry cooler with 20 kW/K positioned at the borefield inlet.
Temperature profile for a dry cooler with 20 kW/K positioned at the borefield inlet.

The regeneration potential is clearly limited by the maximum average fluid temperature here, so increasing the regeneration capacity even more will not decrease the imbalance any further. However, we still have 12 MWh/year of extraction imbalance left. There are two ways to solve this issue: one is to shorten the simulation horizon and the other is to increase your maximum allowed fluid temperature.

Shorter simulation horizon

The simulation horizon, which was previously set to 4380 hours (exactly half a year), determines how far into the future the algorithm looks. Regenerating the ground in the current hour affects the hours, weeks and even months to come. Therefore, if we regenerate too much before summer, the ground temperature can rise too high, thereby destroying any passive cooling potential.

To quantify this effect, let us simulate with a simulation horizon of just 500 hours, which is less than a month. Doing so removes the entire imbalance (now regenerating the full 89 MWh/year) and gives the temperature profile below.

Temperature profile for a dry cooler with 20 kW/K with a simulation horizon of 500 hours.
Temperature profile for a dry cooler with 20 kW/K with a simulation horizon of 500 hours.

As can be seen, the maximum average fluid temperature limit is crossed, with a maximum fluid temperature of 16.4 °C. However, the temperature violation is only 1 Kh, meaning that it only occurs for 2.5 hours each year (a 0.4 K difference for 2.5 hours gives exactly 1 Kh of temperature violation), which is negligible in most cases. The resulting regeneration profile is shown below.

Regeneration graph for a dry cooler with 20 kW/K with a simulation horizon of 500 hours.
Regeneration graph for a dry cooler with 20 kW/K with a simulation horizon of 500 hours.

When the regeneration graph above is compared to the case with a simulation horizon of 4380 hours, it is clear that there is now much more regeneration in summer and that the period without regeneration has become shorter. This is precisely the effect of a shorter simulation horizon, which can also be interpreted as a less strict regeneration simulation.

Different regeneration algorithms

Another way of increasing the regeneration capability of the same 20 kW/K dry cooler is to increase the maximum allowed fluid temperature to 18 °C. This can be done, for example, by changing the emission system in your building so that the same summer comfort can be guaranteed with a higher fluid temperature. With this maximum allowed average fluid temperature of 18 °C, let us now consider the four different regeneration algorithms: yearly, simulation period, proceeding horizon and proceeding horizon +.

Yearly

As explained in above, the goal of the yearly regeneration algorithm is to reduce the imbalance in each year individually. The resulting regeneration profile is shown below.

Regeneration graph for a dry cooler with 20 kW/K with the yearly algorithm.
Regeneration graph for a dry cooler with 20 kW/K with the yearly algorithm.

In the regeneration graph above, it is clear that, due to the higher allowed fluid temperature, the regeneration can now also occur during the summer itself. Only one high cooling peak is avoided in order to stay below 18 °C. What is interesting, however, is that the regeneration apparently stops in September. This implies that, with the 20 kW/K dry cooler, the entire 89 MWh/year of regeneration has already happened by September, leaving us with a perfectly balanced borefield. The corresponding temperature profile is shown below.

Temperature profile for a dry cooler with 20 kW/K with the yearly algorithm.
Temperature profile for a dry cooler with 20 kW/K with the yearly algorithm.

Simulation period

Instead of looking at the imbalance from year to year, it is also possible to look at the cumulative imbalance for the entire simulation period. That is exactly what the ‘simulation period’ algorithm does. The resulting regeneration graph is shown below.

Regeneration graph for a dry cooler with 20 kW/K with the simulation period algorithm.
Regeneration graph for a dry cooler with 20 kW/K with the simulation period algorithm.

When the simulation period algorithm is selected, the same 89 MWh/year (on average) of regeneration can be obtained, but in a slightly different way. As can be seen in the profile above, the regeneration does not stop in September. Instead, the dry cooler keeps injecting heat into the ground until, sometime before the summer of the fifth year, the entire imbalance has been compensated for and regeneration is no longer needed. This gives the temperature profile below.

Temperature profile for a dry cooler with 20 kW/K with the simulation period algorithm.
Temperature profile for a dry cooler with 20 kW/K with the simulation period algorithm.

In the temperature profile above, the difference from the yearly algorithm is clearly visible in the last year. Here, the temperature profile shows no regeneration from April of the fifth year onwards, leading to much lower cooling temperatures and, for that particular year, an extraction-dominated imbalance. However, in the first four years, there is much more regeneration, as shown by the higher fluid temperatures in autumn compared with the yearly algorithm.

The simulation period algorithm is the best way to show what a specific regeneration technology is capable of, since all the other methods are limited either by the yearly imbalance or by the proceeding imbalance (as will be discussed in the next two subsections).

Proceeding horizon

The two algorithms above have the advantage that they can anticipate the imbalance, in the current year and in the entire simulation period respectively. That way, they can maximise their regeneration capabilities. In reality, however, we do not have such perfect information about the future imbalance. Therefore, a proceeding horizon methodology can be used, which only regenerates the imbalance that has already occurred up to the current hour. The regeneration graph is shown below.

Regeneration graph for a dry cooler with 20 kW/K with the proceeding horizon algorithm.
Regeneration graph for a dry cooler with 20 kW/K with the proceeding horizon algorithm.

The proceeding horizon algorithm has yet another shape, and what is interesting is that, in the first year, the regeneration now stops in July instead of September, as with the yearly algorithm. This is because in July, the cumulative imbalance from January up to that point has been fully compensated, and since the algorithm cannot anticipate future imbalance, it stops there. Only in winter will it start regenerating again, since there is once more some extraction load.

However, this approach means that we are always reacting to the imbalance instead of anticipating it, which means that we only regenerate 83 MWh/year on average, leaving an average imbalance of 6 MWh/year. The corresponding temperature profile is shown below, where the point at which the regeneration stops is clearly visible.

Temperature profile for a dry cooler with 20 kW/K with the proceeding horizon algorithm.
Temperature profile for a dry cooler with 20 kW/K with the proceeding horizon algorithm.

Proceeding horizon +

As a last option, the proceeding horizon + algorithm will be discussed. As the name suggests, this is an extension of the proceeding horizon algorithm, but with the option of regenerating in both injection and extraction. As mentioned above, the proceeding horizon algorithm stopped in summer because the cumulative imbalance was completely regenerated.

However, in July and August there was also an injection-dominated imbalance that could be compensated for. The proceeding horizon algorithm, however, only regenerates in the direction of the general imbalance (in this example, extraction-dominated), so it ignores the ‘local imbalance’ in summer. The proceeding horizon + algorithm does not, which results in the regeneration graph below.

Regeneration graph for a dry cooler with 20 kW/K with the proceeding horizon + algorithm.
Regeneration graph for a dry cooler with 20 kW/K with the proceeding horizon + algorithm.

The graph above clearly shows that, whereas the proceeding horizon algorithm simply stopped regenerating, the proceeding horizon + approach switches to extracting heat from the ground after summer, giving us both extraction and injection regeneration in this case. Interestingly, however, the resulting imbalance is exactly the same in both cases (proceeding horizon and proceeding horizon +): 6 MWh/year. The corresponding temperature profile is given below.

Temperature profile for a dry cooler with 20 kW/K with the proceeding horizon + algorithm.
Temperature profile for a dry cooler with 20 kW/K with the proceeding horizon + algorithm.

In the temperature profile above, a difference in fluid temperature between the proceeding horizon and proceeding horizon + algorithms is visible in autumn, where the latter lowers the fluid temperature slightly.

The advantage of the proceeding horizon + algorithm over the standard proceeding horizon algorithm is that the fluid temperatures are more levelled, since local imbalances are also accounted for. This can potentially lead to a higher efficiency in heating and cooling.

Conclusion

In this chapter, the focus was on regeneration, an alternative to hybridisation to counteract the imbalance in geothermal borefields. Where hybridisation takes part of the load away from the borefield, regeneration adds extra heat injection or extraction so that the imbalance is compensated for. Five categories of regeneration technologies were discussed: constant power, constant temperature, solar thermal, dry coolers and a known regeneration profile.

Afterwards, the theoretical background was explained, with the three rules for regeneration, the position of the regeneration technology (at the borefield inlet or outlet) and the four regeneration algorithms (yearly, simulation period, proceeding horizon and proceeding horizon +), each corresponding to a different control strategy in practice.

Lastly, an extensive example of a residential building with a dry cooler was worked out. It was shown that the pinch temperature, the dry cooler size, the simulation horizon and the maximum fluid temperature all have a large impact on the resulting regeneration and that a larger regeneration technology does not always lead to more regeneration. Just like with most things in geothermal design, there is no silver bullet, so it is important to play around with the different options for your particular project.

Questions

Imagine you have the option to use an air-source heat pump next to your geothermal system to lower your geothermal imbalance towards extraction. Does it matter whether you use it as a hybrid technology or as a regeneration one, since both solve the same issue in the end? Can you find reasons for when to opt for one or the other?
The only thing to check is consistency. Elsewhere in the chapter, you write it as “proceeding horizon +”, in lowercase and with a space before the “+”.
With the maximum average fluid temperature of 18 °C, what could be the size of the dry cooler so that the imbalance is smaller than 5 MWh/year towards extraction?
Now simulate the regeneration not with a dry cooler but with two types of PVT panels: glazed ($a_0$ = 0.429 and $a_1$ = 11.5 W/(m²K)) and unglazed ($a_0$ = 0.473 and $a_1$ = 19.91 W/(m²K)). Use a surface area of 50 m². What differences do you notice between them?

References

  • Peere, W. (2027). Three rules for regeneration and shallow geothermal borefields. In proceedings of GeoTHERM Expo & Congress, 25-26 February, 2027, Offenburg, Germany. [abstract accepted]
  • Ecoforest. (n.d.). Air units: High power AU range. Retrieved November 23, 2026, from https://ecoforest.com/en/products/news/air-units-high-power-au-range/
  • AQSOL Solar e.K. (n.d.). Solare Poolbeheizung vom Testsieger. Retrieved November 23, 2026, from https://aqsol.de/

Downloads

  • Download the CSV file of the residential building here.
  • Download the EPW file here.
  • Download the GHEtool report here.